OPERATING GUIDELINES FOR SMF / VRLA BATTERIES

    •   Constant voltage current limited charging as per the charging specification table – 3 for optimum performance / life.
    •   For operating temperature more or less 25°C, apply the correction factor for charging voltage as per as the table given below.
    •   Immediate recharging recommended after discharge to avoid battery capacity loss.
    •   For deep discharging application re-charging time to be increased by 1.5 to 2 times for the normal charging (On float 24 hrs and On boost 16 hrs charging) time
            before it undergoes next cycle.
    •   Never use new and old batteries in series. Batteries of different capacities and different manufacturer should never be used in same bank, Parallel string not
            recommended. Avoid bypassing the lower cutoff protection which will allow the battery to go into deep discharge.
    •   Continuous boost charging is not recommended for more than 24 hours to avoid over charging.
    •   Replace any defective if abnormalities noticed on voltage, heat, electrolyte leakage or physical deformation.
    •   If the battery is stored more than 03 months, boost charging for 09 hours recommended before the battery is put in deformation.
    •    Once in 06 month the batteries should be equalization charge at 13.8 volts per modules.
    •   Do not reverse charge the battery.
    •   Never bend the terminals not solder directly.
    •   Use proper size connector for the inter connection and end connection. Avoid loose/bad connection.
    •   Battery shall be secured against impact, vibration and heat source.
    •   Keep top of the battery clean and dry.
    •   Do not short the terminal directly.
    •   Transport the battery in the upright position.



      Caution

      •   Keep the battery away from sparks, cigarettes and open flame.
      •   Avoid the metallic contact across the terminal.
      •   In case of acid leakages due to container crack, do wash it with water immediately.
      •   Do not install the battery without removing the packing cover.
        Avoid charging in air tight container.

      ADVANTAGES & FEATURES
      High quality and reliability : The tough value of these rechargeable batteries is designed to provide excellent performance. These can withstand overcharge, over discharge, and resisting vibration and shock. Before the dispatch of the products, these are GOLD STAR tests each battery thoroughly based on various parameters including 100% High rate discharge test.
      Exceptional deep Discharge recovery : GOLD STAR SMF VRLA batteries have exceptional discharge recovery, even after deep or prolonged discharge.
      No corrosive gas generation : The batteries are sealed properly by ultra sonic method, so that there is no corrosive gas generated during normal usage.
      Long service life : GOLD STAR batteries based on unique grid technology, allow composition, correct AGM compression and specially designed for standby use. Thus, these ensure to provide long services life.

      Maintenance- free operation : The batteries are know for their maintenance free operation, wherein there is no need to check the specific gravity of the electrolyte or to add water during the service


    Table 1 - SPECIFIATION 
    Model Voltage (Volts) Capacity Ah @ 20hr Dimensions ( 2mm) Weight ( 5%)
    Length Width Height Total Height
    GSV7.2 12 7.2 152 65 95 100 2.3
    GSV10 12 10 152 99 95 100 3.6
    GSV12 12 12 152 99 95 100 4
    GSV18 12 18 180 77 171 171 6.8
    GSV24 12 24 180 77 171 171 7.2
    GSV26 12 26 165 125 175 180 8.7
    GSV42 12 42 197 165 170 175 13.5
    GSV65 12 65 350 167 165 165 21.2
    GSV100 12 100 406 172 207 236 32

    Tabel 2 - DISCHARGE CHARACTERISTICS
    Model Voltage (Volts) Capacity Ah @ 27hr Dischrage characteristic in Amps
    1C to 9.6V (>27 MInutes) C20 to 10.5V C10 to 10.5V C5 to 10.5V C3 to 10.2V C1 to 10.2V
    GSV7.2 12 7.2 7.2 0.36 0.65 1.1 1.6 3.3
    GSV10 12 10 10 0.5 0.9 1.5 2.2 4.5
    GSV12 12 12 12 0.6 1.1 1.8 2.6 5.5
    GSV18 12 18 18 0.9 1.7 2.7 3.9 8.5
    GSV24 12 24 24 1.2 2.2 3.6 5.2 11
    GSV26 12 26 26 1.3 2.4 4 6.2 12
    GSV42 12 42 42 2.1 3.8 6.4 9 19
    GSV65 12 65 65 3.25 6 10 14.3 30
    GSV100 12 100 100 5 9 15 21.5 45


    Table 3 - CHARGING CHARACTERISTICS
    Charging Voltage @ 27C
    Available Charging Mode Voltage 
    Stand By 13.5 to 13.8 V
    Cycle 14.1 to 14.4 V
    Charging Current Max. 20% of rate capacity
    Recommended over volatge trip at 14.1V and under voltage at 10.5V per module in the charger circuit
    Temperature compensation coefficient - Reduce 3mv / cell per °C increase in temperture in standby use and 5mv / cel per °C cycle use. Recommended operating temperature is 10°C - 35°C

    Battery cyclic life is highly dependent on the depth of discharge that the battery experiences during each cycle. The various number of cycles related to the depth of discharge is shown  in the graph.

    The capacity of a GOLD STAR battery is the amount of electrical energy that can be obtained from a full changed cell. The capacity is expressed in Ampere Hours(AH). The capacity value is dependent on the discharge current, the temperature during discharge and the final cutoff voltage.

    During storage, batteries gradually lose their capacity due to self – discharge. GOLD STAR’s self – discharge rate is low typically ≤3% month at 25°C. However, it is recommended that specific precautions to taken to prevent the battery from over self-discharging when it is stored in a cool, dry place. They should not be exposed to sunshine, or other source of radiant heat like radiators,   heating units, stoves, stem, pipes etc. Recommended storage temperature is 10°C to 25°C. Humidity should be as low as possible.